Compliance News: Alcohol-Based Hand-Rub Dispenser Placement


By Robert Trotter, CBO, CFM




Health care organizations should already be familiar with the current code-based requirements of NFPA 101®, Life Safety Code® and The Joint Commission (TJC) regarding the placement of Alcohol-Based Hand-Rub (ABHR) Dispensers. TJC is now allowing ABHR dispensers to be placed according to the requirements of the 2009 and 2012 editions of NFPA 101®,Life Safety Code®. The primary change from previous TJC requirements is the reduction of the minimum measurements from the ignition source to the dispenser. LSC Sections 18/19.3.2.6 (7) state: Dispensers shall not be installed in the following locations: 


  • Above an ignition source within 1 inch (25 mm) horizontal distance from each side of the ignition source.
  • To the side of an ignition source within a 1 inch (25 mm) horizontal distance from the ignition source.
  • Beneath an ignition source within a 1 inch (25 mm) vertical distance from the ignition source.

For ignition sources such as duplex receptacles and light switches the measurements are taken from the side edges of the ignition source coverplate as depicted in the diagram.

Tuesday, January 24, 2012

Oxygen Storage


If storage under 300 cubic feet can be “open to the corridor” is there still a requirement to install a sign if the oxygen is stored in an enclosure versus being stored open to the corridor?  Would this be considered a Life Safety or an Environment of Care issue?

Monday, January 23, 2012

Blocked Exit Passageway

Our nursing department is conducting training and we need to have various types of equipment lined up along the corridor during that time for training.  Is there a way this setup could be legally permitted for a week or two?

Thursday, January 19, 2012

Surgery Fire Plans

Our director of surgery is wanting to create their own plan.  Is it common for a facility to have a fire plan specific for surgery? 

Wednesday, January 18, 2012

Tuesday, January 17, 2012

Recyclable Paper Containers


We keep large receptacles for recyclable paper in our nursing stations. The dimensions of the receptacles are approximately 18'' x 18'' x 36''. Is recycled paper considered to be “waste” by the Joint Commission? Is it okay to keep these receptacles in the hallway of a nursing unit?

Friday, January 13, 2012

Ceilings and Grab Bars

Our hospital received a supplemental recommendation for EC.1.10 in our psychiatric unit. The reference was to the potential for hanging oneself from grab bars and ceilings. The bathrooms have hard ceilings, but the patient rooms do not. I see that there is a requirement in the 2001 AIA Guidelines for Design and Construction for tamper resistant ceilings. Would clips of the tiles suffice? Also, no mention is made of grab bars.


Tuesday, January 10, 2012

AIA Guidelines for TJC

What year of AIA Guidelines does The Joint Commission follow?  If we are renovating a critical access hospital that will follow state rules and regulations, do we have to follow TJC?


Monday, January 9, 2012

Wednesday, January 4, 2012

Tuesday, January 3, 2012

ABHR Placement

Has TJC adopted the NFPA 101, 2009 requirements for placing ABHR dispensers with the 1-inch in lieu of 6-inch spacing from ignition sources?