Friday, March 30, 2012
Compliance News: CMS Eases Hospital Corridor Clutter Waiver Process
By David Stymiest, PE, CHFM, FASHE
CMS issued new Survey and Clarification Memo # S&C-12-21-LSC, which applies to both hospitals and nursing homes, on March 9, 2012. CMS is easing its process for obtaining waivers in order to take advantage of four provisions in the NFPA 101 Life Safety Code© 2012 edition. CMS will now “allow providers to implement these four changes by considering waivers of the current LSC requirements found in the 2000 edition of the LSC without showing ‘unreasonable hardship’.” The four 2012 Life Safety Code© portions referenced by CMS are 18/19.2.3.4 under Capacity of Means of Egress; 18/19.3.2.5.2, 18/19.3.2.5.3, 18/19.3.2.5.4 and sections 18/19.3.2.5.5 under Cooking Facilities; 18/19.5.2.3(2), (3) and (4) under Heating, Ventilating, and Air Conditioning; and 18/19.7.5.6 under Furnishings, Mattresses, and Decorations. CMS stated “Due to the complex nature of some of the requirements, each waiver request will have to be evaluated separately in the interest of fire safety and to ensure that the facility has followed all LSC requirements and the equipment has been installed properly by the facility.”
ASHE members should have already received both an ASHE Advocacy Alert and Issue Brief regarding this topic. Since CMS waivers are issued after adverse findings during validation surveys, our recommendation is that organizations stay tuned and follow the development of this issue. As of this writing The Joint Commission has not commented publically.
Compliance News: The NFPA 110 Installation Acceptance Test
By David Stymiest, PE, CHFM, FASHE
Many hospitals are installing new or replacement emergency power systems. NFPA 110 requires a special testing sequence before the system may be used.
Although the NFPA 110-2005 edition is referenced by the 2010 FGI Guidelines for Design and Construction of Healthcare Facilities, readers should review the updated and considerably improved Installation Acceptance Test in Section 7.13 of NFPA 110-2010 (www.nfpa.org/110). The 2010 update was rewritten to clarify the intent of the testing. If a project team is considering deviating from verbatim NFPA 110 requirements because of facility-specific differences, all necessary authority having jurisdiction (AHJ) approvals should be obtained.
Some of the major requirements of the NFPA 110-2010 Installation Acceptance Test include:
Tuesday, March 20, 2012
Transfer Switch Location Battery Lighting
QUESTION: Where is the requirement for battery lights at transfer switch locations? When did that requirement first appear?
Thursday, March 8, 2012
Wednesday, March 7, 2012
Penetrations in 2-HR Fire Barriers
Tuesday, March 6, 2012
Mural Painted Exit Access Doors
Life Safety Tip from Bob Trotter, CBO, CFM, MCP
Mural Painted Exit Access Doors
Be careful about where painted murals are located. Exit access and exit doors with painted murals for decorative effect are not acceptable, as casual occupants might not be aware of such means of egress even though it is visible. The 2000 edition of NFPA 101®, Life Safety Code® 7.5.2.2 states “Exit access and exit doors shall be designed and arranged to be clearly recognizable”.
Mural Painted Exit Access Doors
Be careful about where painted murals are located. Exit access and exit doors with painted murals for decorative effect are not acceptable, as casual occupants might not be aware of such means of egress even though it is visible. The 2000 edition of NFPA 101®, Life Safety Code® 7.5.2.2 states “Exit access and exit doors shall be designed and arranged to be clearly recognizable”.
Monday, March 5, 2012
Improper Exit Arrangement
Life Safety Tip from Bob Trotter, CBO, CFM, MCP
If a temporary partition is installed to separate an area undergoing construction, repair, or improvement operations, alternate EXITS need to be identified. According to LS.01.02.01 Element of Performance 2 of the 2012 Hospital Accreditation Standards “The hospital posts signage identifying the location of alternate exits to everyone affected”. The appropriate action for this scenario would be to cover or remove the EXIT sign and post the (floor plan) signage indicating the location(s) of alternate EXITS.
Thursday, March 1, 2012
Separation of E-Cylinders
Is there a standard that notes that full e-cylinders need to be separated from empty cylinders?
Subscribe to:
Posts (Atom)