Do we need approval or an inspection to move our cooking appliances?
Yes. Cooking appliances that require fire protection need to be evaluated before moving and/or remodeling the kitchen.
According to NFPA 96, Standard for Ventilation Control and Fire
Protection of Commercial Cooking Operations, 1998 edition Section 9-1.2.2 states “Cooking appliances requiring
protection shall not be moved, modified, or rearranged without prior
reevaluation of the fire-extinguishing system by the system installer or
servicing agent, unless otherwise allowed by the design of the
fire-extinguishing system” . The Annex of NFPA 96 states “The effectiveness of an automatic extinguishing system is
affected by the placement of the nozzles. For this reason, it is essential that
cooking appliances be situated in the area in which they were when the
extinguishing equipment was designed and installed. If an appliance is moved
from under the equipment for cleaning or any other reason, it should be
replaced to its original position prior to initiating a cooking operation”.