What is the mesh requirement for cubicle curtains in hospitals?
This only applies to healthcare occupancies and the distance of the sprinkler from the mesh is just as important as the commonly known 18" rule. Please see the code references below.
NFPA 101, Life Safety Code®,
2000 Edition
19.3.5.5*
Newly
introduced cubicle curtains in sprinklered areas shall be installed in
accordance with NFPA 13, Standard for the
Installation of Sprinkler Systems.
Annex A.19.3.5.5
For
the proper operation of sprinkler systems, cubicle curtains and sprinkler
locations need to be coordinated. Improperly designed systems might obstruct
the sprinkler spray from reaching the fire or might shield the heat from the
sprinkler. Many options are available to the designer including, but not
limited to, hanging the cubicle curtains 18 in. (46 cm) below the sprinkler
deflector; using 1/2-in. (1.3-cm) diagonal mesh or a 70 percent open weave top
panel that extends 18 in. (46 cm) below the sprinkler deflector; or designing
the system to have a horizontal and minimum vertical distance that meets the
requirements of NFPA 13, Standard for the Installation of Sprinkler Systems.
The test data that forms the basis of the NFPA 13 requirements is from fire
tests with sprinkler discharge that penetrated a single privacy curtain.
NFPA 13, 1999 Edition, Cubicle Mesh Curtains
Appendix A
A-5-6.5.2.3
The distances given in Table 5-6.5.2.3 were determined through
tests in which privacy curtains with
either a solid fabric or close mesh [1/4 in.
(6.4 mm)] top panel were installed. For broader-mesh
top panels — for example, 1/2 in.
(13 mm) or greater measured on the diagonal — the obstruction of the sprinkler
spray is not likely to be severe and the authority having jurisdiction might
not need to apply the requirements in 5-6.5.2.3.
A-5-6.6
The 18-in. (457-mm) dimension is not intended to limit the
height of shelving on a wall or shelving against a wall in accordance with 5-6.6.
No comments:
Post a Comment