Friday, March 30, 2012
Compliance News: CMS Eases Hospital Corridor Clutter Waiver Process
By David Stymiest, PE, CHFM, FASHE
CMS issued new Survey and Clarification Memo # S&C-12-21-LSC, which applies to both hospitals and nursing homes, on March 9, 2012. CMS is easing its process for obtaining waivers in order to take advantage of four provisions in the NFPA 101 Life Safety Code© 2012 edition. CMS will now “allow providers to implement these four changes by considering waivers of the current LSC requirements found in the 2000 edition of the LSC without showing ‘unreasonable hardship’.” The four 2012 Life Safety Code© portions referenced by CMS are 18/19.2.3.4 under Capacity of Means of Egress; 18/19.3.2.5.2, 18/19.3.2.5.3, 18/19.3.2.5.4 and sections 18/19.3.2.5.5 under Cooking Facilities; 18/19.5.2.3(2), (3) and (4) under Heating, Ventilating, and Air Conditioning; and 18/19.7.5.6 under Furnishings, Mattresses, and Decorations. CMS stated “Due to the complex nature of some of the requirements, each waiver request will have to be evaluated separately in the interest of fire safety and to ensure that the facility has followed all LSC requirements and the equipment has been installed properly by the facility.”
ASHE members should have already received both an ASHE Advocacy Alert and Issue Brief regarding this topic. Since CMS waivers are issued after adverse findings during validation surveys, our recommendation is that organizations stay tuned and follow the development of this issue. As of this writing The Joint Commission has not commented publically.
Compliance News: The NFPA 110 Installation Acceptance Test
By David Stymiest, PE, CHFM, FASHE
Many hospitals are installing new or replacement emergency power systems. NFPA 110 requires a special testing sequence before the system may be used.
Although the NFPA 110-2005 edition is referenced by the 2010 FGI Guidelines for Design and Construction of Healthcare Facilities, readers should review the updated and considerably improved Installation Acceptance Test in Section 7.13 of NFPA 110-2010 (www.nfpa.org/110). The 2010 update was rewritten to clarify the intent of the testing. If a project team is considering deviating from verbatim NFPA 110 requirements because of facility-specific differences, all necessary authority having jurisdiction (AHJ) approvals should be obtained.Some of the major requirements of the NFPA 110-2010 Installation Acceptance Test include:
Tuesday, March 20, 2012
Transfer Switch Location Battery Lighting
QUESTION: Where is the requirement for battery lights at transfer switch locations? When did that requirement first appear?
Thursday, March 8, 2012
Wednesday, March 7, 2012
Penetrations in 2-HR Fire Barriers
Tuesday, March 6, 2012
Mural Painted Exit Access Doors
Life Safety Tip from Bob Trotter, CBO, CFM, MCP
Mural Painted Exit Access Doors
Be careful about where painted murals are located. Exit access and exit doors with painted murals for decorative effect are not acceptable, as casual occupants might not be aware of such means of egress even though it is visible. The 2000 edition of NFPA 101®, Life Safety Code® 7.5.2.2 states “Exit access and exit doors shall be designed and arranged to be clearly recognizable”.
Monday, March 5, 2012
Improper Exit Arrangement
Life Safety Tip from Bob Trotter, CBO, CFM, MCP
If a temporary partition is installed to separate an area undergoing construction, repair, or improvement operations, alternate EXITS need to be identified. According to LS.01.02.01 Element of Performance 2 of the 2012 Hospital Accreditation Standards “The hospital posts signage identifying the location of alternate exits to everyone affected”. The appropriate action for this scenario would be to cover or remove the EXIT sign and post the (floor plan) signage indicating the location(s) of alternate EXITS.
Thursday, March 1, 2012
Separation of E-Cylinders
Is there a standard that notes that full e-cylinders need to be separated from empty cylinders?
Wednesday, February 29, 2012
In Case of Fire, Resolve to Make a Plan in 2012
"In Case of Fire, Resolve to Make a Plan in 2012"
This article first appeared in the February 2012 issue of Nashville Medical News.
By Robert Trotter, CBO, CFM, MCP
In a February 2009 report, the National Fire Protection Association (NFPA)
identified that during 2003-2006, municipal fire departments responded to an
estimated 3,750 structure fires in medical, mental health, and substance abuse
facilities, annually. These fires resulted in one civilian death, 57 civilian
injuries, and $26.9 million in direct property damage. While no amount of money
can account for the loss of a loved one, the United States Consumer Product
Safety Commission (CPSC) assigns a statistical value per life of $5 million; and
according to its Injury Cost Model, the estimated cost of a fire-related injury
is about $56,000 per incident. Therefore, the average total estimated cost of
these healthcare facility fires was $34.2 million.
Every well-managed healthcare organization should have, in effect and available to all supervisory personnel, written copies of a plan for the protection of all persons in the event of fire, for their evacuation to areas of refuge, and for their evacuation from the building when necessary.
To read the entire article, please click here.
In a February 2009 report, the National Fire Protection Association (NFPA)
identified that during 2003-2006, municipal fire departments responded to an
estimated 3,750 structure fires in medical, mental health, and substance abuse
facilities, annually. These fires resulted in one civilian death, 57 civilian
injuries, and $26.9 million in direct property damage. While no amount of money
can account for the loss of a loved one, the United States Consumer Product
Safety Commission (CPSC) assigns a statistical value per life of $5 million; and
according to its Injury Cost Model, the estimated cost of a fire-related injury
is about $56,000 per incident. Therefore, the average total estimated cost of
these healthcare facility fires was $34.2 million.Every well-managed healthcare organization should have, in effect and available to all supervisory personnel, written copies of a plan for the protection of all persons in the event of fire, for their evacuation to areas of refuge, and for their evacuation from the building when necessary.
To read the entire article, please click here.
Tuesday, February 28, 2012
Temporary Electrical Wiring
Life Safety Tip from Bob Trotter, BS, MCP
Temporary
Electrical Wiring
According to NFPA 70, National Electrical Code, 1999 edition temporary wiring is defined as “Approved wiring for power and lighting during a period of construction, remodeling, maintenance, repair, or demolition, and decorative lighting, carnival power and lighting, and similar purposes”. The NEC requires temporary wiring to be removed immediately upon completion of construction or purpose for which the wiring was installed.
According to NFPA 70, National Electrical Code, 1999 edition temporary wiring is defined as “Approved wiring for power and lighting during a period of construction, remodeling, maintenance, repair, or demolition, and decorative lighting, carnival power and lighting, and similar purposes”. The NEC requires temporary wiring to be removed immediately upon completion of construction or purpose for which the wiring was installed.
Saturday, February 25, 2012
Continuous Compliance - Maintaining a constant state of regulatory readiness
Continuous compliance - Maintaining a constant state of regulatory readiness
This article first appeared in the May 2011 issue of HFM Magazine.
By David L. Stymiest, P.E., CHFM, FASHE
Continuous compliance also has been called continuous survey readiness. It involves proactively maintaining a safe health care environment conducive to high-quality patient care. It essentially means having staff at all levels doing the right things for the right reasons because they understand those reasons.Just about all accrediting agencies conduct unannounced surveys or inspections. Even when organizations think they know approximately when the next unannounced survey is due, there is the potential for random unannounced surveys or a for-cause survey. Thus, continuous survey readiness is crucial. Ongoing training and thorough staff involvement in compliance activities are essential because key managers might be unavailable when the surveyors arrive.
To read the entire article, please click here
Thursday, February 23, 2012
Daily checks on Airborne Infectious Isolation (AII) rooms
CDC is often listed as the source of guidelines for daily checks on Airborne Infectious Isolation (AII) rooms.
The document with the CDC guidelines is "Centers for Disease Control and Prevention. Guidelines for Preventing the Transmission of Mycobacterium tuberculosis in Health-Care Settings, 2005. MMWR 2005;54(No. RR-17)" and is at the following link:
http://www.cdc.gov/mmwr/pdf/rr/rr5417.pdf
If you go to the CDC website and download the linked document, you will see the following wording in the right column on page 19 (PDF) or 17 (DOCUMENT PAGE #):
"Settings with AII Rooms
Health-care personnel settings with AII rooms should
• keep doors to AII rooms closed except when patients,
HCWs, or others must enter or exit the room (118);
• maintain enough AII rooms to provide airborne precautions
of all patients who have suspected or confirmed TB
disease. Estimate the number of AII rooms needed based
on the results of the risk assessment for the setting;
• monitor and record direction of airflow (i.e., negative pressure)
in the room on a daily basis, while the room is being
used for TB airborne precautions. Record results in an
electronic or readily retrievable document;"
Continuation not inserted here. Refer to the referenced document for all guidelines.
Styrofoam Sound Barrier
Life Safety Tip from Bob Trotter, BS, MCP
Styrofoam Sound Barrier
The Styrofoam™ sheets applied to the walls of this mechanical room being use as a sound barrier must meet the interior wall and ceiling finish requirements of the 2000 edition of NFPA 101®, Life Safety Code®. For Health Care Occupancies Section 19.3.3.2 states the following:
19.3.3.2 Interior wall and ceiling finish materials
complying with 10.2.3 shall be permitted as follows: (1) Existing materials — Class A or Class B.
Exception: In rooms protected by an approved, supervised automatic sprinkler system, existing Class C interior finish shall be permitted to be continued to be used on walls and ceilings within rooms separated from the exit access corridors in accordance with 19.3.6.
It is expected that this type exposed product for this application will not meet the interior finish requirements.
Styrofoam Sound Barrier
The Styrofoam™ sheets applied to the walls of this mechanical room being use as a sound barrier must meet the interior wall and ceiling finish requirements of the 2000 edition of NFPA 101®, Life Safety Code®. For Health Care Occupancies Section 19.3.3.2 states the following:
Exception: In rooms protected by an approved, supervised automatic sprinkler system, existing Class C interior finish shall be permitted to be continued to be used on walls and ceilings within rooms separated from the exit access corridors in accordance with 19.3.6.
It is expected that this type exposed product for this application will not meet the interior finish requirements.
Wednesday, February 22, 2012
Conflicting Exit Signs
Life Safety Tip from Bob Trotter, BS, MCP
Conflicting Exit Signs
This
scenario exists at the bottom of an EXIT stair enclosure. The original EXIT
sign did not indicate the direction of egress travel. Therefore the more modern
EXIT sign was installed with the left Chevron indicating the direction of
egress travel. However, the original sign should have been removed to eliminate
the conflict that could pose risk to life safety.