I
find no requirement for above ceiling low voltage wiring to be plenum rated
unless it is located in an air plenum or riser (penetrating more than one floor
or in shaft, NFPA 70) (101-3.3.150). An air plenum includes any space used as
part of the air distribution system.
Above
ceiling wiring must be resistant to the spread of fire (70-800.49 &
70-800.51). Acceptable types are listed in chapter 800. There are a number of
installation guidelines outlined in the NEC chapter 800.
NFPA
101(2000) 3.3.150 Plenum.
A
compartment or chamber to which one or more air ducts are connected and that
forms part of the air distribution system.
NFPA
70 (NEC) addresses permitted wiring types. Many changes took place in the NEC
between the 1999 edition and the 2002 edition. I tried to stay away from
changes. The following are excerpts that did not change. There are many
exceptions for specific situations. Refer to the NEC for more
information.
NFPA
70(2002) 800.49 Fire Resistance of Communications Wires and Cables.
Communications
wires and cables installed as wiring within a building shall be listed as being
resistant to the spread of fire in accordance with 800.50 and 800.51.
NFPA
70(2002) 800.50 Listing, Marking, and Installation of Communications Wires and
Cables.
Communications
wires and cables installed as wiring within buildings shall be listed as being
suitable for the purpose and installed in accordance with 800.52. Communications
cables and undercarpet communications wires shall be marked in accordance with
Table 800.50. The cable voltage rating shall not be marked on the cable or on
the undercarpet communications wire.
NFPA
70(2002) 800.51 Listing Requirements for Communications Wires and Cables and
Communications Raceways.
Communications
wires and cables shall have a voltage rating of not less than 300 volts and
shall be listed in accordance with 800.51(A) through (J), and communications
raceways shall be listed in accordance with 800.51(K) through (L). Conductors in
communications cables, other than in a coaxial cable, shall be
copper.
NFPA
70(2002) 800.52 Installation of Communications Wires, Cables, and
Equipment.
Communications
wires and cables from the protector to the equipment or, where no protector is
required, communications wires and cables attached to the outside or inside of
the building shall comply with 800.52(A) through (E).
NFPA
70(2002) 830.54 Medium Power Network-Powered Broadband Communications System
Wiring Methods.
Medium
power network-powered broadband communications systems shall be installed within
buildings using listed Type BM or Type BMR, network-powered broadband
communications medium power cables.
(A)
Ducts, Plenums, and Other Air-Handling Spaces. Section 300.22 shall
apply.
(B)
Riser. Cables installed in vertical runs and penetrating more than one floor, or
cables installed in vertical runs in a shaft, shall be Type BMR. Floor
penetrations requiring Type BMR shall contain only cables suitable for riser or
plenum use.
NFPA
70(2002) 300.22 Wiring in Ducts, Plenums, and Other Air-Handling
Spaces.
The
provisions of this section apply to the installation and uses of electric wiring
and equipment in ducts, plenums, and other air-handling spaces.
No comments:
Post a Comment